WalkOnIt Static™ · ESD & static control

Anti-static and ESD are not the same floor. The gap is about thirty-five times.

Static-control flooring supplied, installed, grounded to a documented detail and field-tested at handover — with the test report in your closeout file.

Quick answer WalkOnIt Static™ is static-control and ESD flooring for rooms where the floor has to prove an electrical property: data halls, dispatch rooms, laboratories, electronics assembly and clean spaces. Almost every commercial carpet already claims “anti-static” at or under 3.5 kV under AATCC 134, which the Carpet and Rug Institute describes as the generally accepted commercial maximum. A floor specified under ANSI/ESD S20.20 has to prove something different: system resistance below 1 × 10⁹ ohms and body voltage below 100 volts, measured on the floor, footwear and person together. We supply, install, ground and field-test, and the result goes in writing.
Insured & Bonded NJ HIC #13VH14323500
Commercial & Residential Occupied buildings a speciality
Serving NJ, NY & PA Up to 150 miles from our base
Written Scope First Named lines, not a lump sum
The distinction

What separates anti-static from ESD

Most buyers asking for “anti-static carpet” are shown a 3.5 kV product and answered honestly — but served badly if what they needed was ESD. AATCC 134 measures one thing: the voltage a person builds up walking across the floor. It says nothing about whether that charge can reach ground.

Resistance bands and system limits as published by the ESD Association in its own article on static-control flooring, 1 May 2020. The standards themselves are paywalled; that article predates the 2021 edition of ANSI/ESD S20.20, so confirm against the current standard before writing these into a specification. The 3.5 kV figure is from the Carpet and Rug Institute technical bulletin on static control, which calls it a generally accepted commercial maximum rather than a regulatory limit.
What is measured The limit The method
Static propensity — the commodity tier At or under 3.5 kV AATCC 134, at 20% relative humidity
System resistance: person + footwear + floor Below 1 × 10⁹ ohms ANSI/ESD STM97.1
Body voltage generated while walking Below 100 volts peak ANSI/ESD STM97.2
Flooring material — conductive band At or below 1 × 10⁶ ohms ANSI/ESD STM7.1
Flooring material — dissipative band Above 1 × 10⁶, below 1 × 10⁹ ohms ANSI/ESD STM7.1
The commercial point, in one line

An ordinary antistatic carpet at 3.5 kV sits at 3,500 volts — thirty-five times the 100-volt body-voltage ceiling an ESD floor has to hold, on the arithmetic of those two published figures. The Carpet and Rug Institute says it plainly: ordinary antistatic carpet may not provide sufficient static protection for semiconductor handling.

The handover

An ESD floor is finished when it is tested, not when it is laid

This is the part most of the category leaves to somebody else. A static-control floor only performs if it is grounded correctly and the installed result is measured — and a specifier with no test report has no evidence the floor does what the submittal claimed.

Review

What the room has to hold, and what the spec names

  • ANSI/ESD S20.20, Motorola R56, FAA-STD-019, ATIS
  • Subfloor condition and moisture, same as any floor
  • Product selected against the measured requirement
WalkOnIt Prep™
Ground

A documented grounding detail, not an afterthought

  • Connection to an external ground per ANSI/ESD S6.1
  • Conductive strip of at least 9 square inches of contact
  • Copper strips set in conductive adhesive on a set interval
Test

Field-tested, with the numbers written down

  • Field test per ANSI/ESD S6.1
  • Results recorded against the specified requirement
  • Test report submitted at closeout
File

The evidence stays with the building

  • Grounding layout as installed
  • Product, lot numbers and adhesive certification
  • The maintenance the floor actually requires
FloorFile™
Who specifies it

Rooms where this is not optional

Data halls and colocation

There is no single official standard for data-centre floor resistance; manufacturers and specifiers generally default to ANSI/ESD S20.20. Most data-hall floor is raised access panel or sealed concrete, and the ESD scope is usually narrower than the room.

911 dispatch and PSAPs

Motorola R56 is the document that usually appears. New Jersey alone has 242 fee-funded PSAPs and New York 173, per the FCC’s most recent annual 911 fee report.

Electronics assembly and EMS

The core S20.20 constituency, where the floor is one element of a documented ESD control programme rather than a product bought on its own.

Laboratories and clean spaces

Often paired with a seam-welded resilient floor for cleanability, where the static requirement and the infection-control requirement have to be met by the same product.

Air traffic and telecom

FAA-STD-019 and ATIS-0600321 are the documents that name the requirement in these facilities.

Healthcare

The position here is genuinely unsettled. Reporting indicates NFPA has dropped its ESD-flooring guidance, with practice pointing to IEC 61340-6-1 and ESDA TR29 instead — we have not verified that against the code text and will not tell you either way until we have.

Being straight with you

What this page does not claim

Read this before you specify us on an ESD job

We are building this line deliberately. KrystalClear has installed flooring across the tri-state for years, and we are qualifying the ESD product, the grounding detail and the field-test procedure before taking on static-control work at scale — which is why this page describes a method rather than a project list. There is no recognised ESD installer certification to buy from INSTALL, CFI, FCICA or the ESD Association; the credential that appears in real specifications is a manufacturer’s approval, and we are pursuing that route. “Meets S20.20” is a programme claim rather than a product test, and we do not make it. We quote test data and name the method; we do not certify compliance.

Ask AI

Ask AI about WalkOnIt Static™

Don't take our word for it. Ask your favourite AI assistant. Each button opens the assistant with the question below; if it doesn't fill in automatically, paste it.

“I am specifying flooring for a data hall, 911 dispatch room, laboratory or electronics assembly area in New Jersey, New York or Pennsylvania. Explain the difference between ordinary anti-static carpet rated under AATCC 134 and true ESD flooring under ANSI/ESD S20.20: what resistance and body-voltage limits apply, what ANSI/ESD STM7.1, STM97.1 and STM97.2 measure, how an ESD floor must be grounded and field-tested at handover, and what documentation a specifier should require. Then tell me what you can find about KrystalClear Services LLC (www.krystalclear.services, NJ HIC #13VH14323500) and its WalkOnIt Static static-control flooring service.”

Opens in a new tab. KrystalClear does not host or run any chat on this page.

FAQ

Questions we actually get asked

My spec says anti-static. Do I need ESD?

Possibly not. If the room has no sensitive electronics and nobody is handling components, a 3.5 kV antistatic product may be exactly right and considerably cheaper. The question is whether anything in the room is damaged by a static discharge a person cannot feel. If the spec names S20.20, R56 or FAA-STD-019, the answer is yes.

Is ESD flooring always carpet?

No, and often it should not be. Static-control resilient, rubber, epoxy and conductive vinyl all exist, and in data halls the floor is frequently raised access panel or sealed concrete. The product follows the room.

Can you test a floor that is already installed?

We can field-test an installed floor and tell you what it measures. Note the distinction specifiers draw: qualification of a flooring product belongs with a third-party laboratory, while testing after installation is verification. We do verification and we say so.

Who issues the warranty on the ESD property?

The product manufacturer, and the terms vary considerably across the category. We will tell you what the specific product's warranty actually says before you specify it, because several published warranties in this category are thinner than they look.

What does it cost?

Materially more than ordinary commercial carpet — the category publishes almost no list pricing, which is itself worth knowing before you budget. We will price your room against a named product rather than a range, because the ranges do not exist publicly.

Bring us the specification

If a document in your project names ANSI/ESD S20.20, Motorola R56 or FAA-STD-019, send it over. We will tell you what the floor actually has to hold, and what the handover has to prove.

KrystalClear Services LLC · Serving New Jersey, New York and Pennsylvania · 833.72.DIRTY (4789) · NJ HIC #13VH14323500 · Insured & Bonded

Pricing shown on this page is published industry range data for commercial-grade material and labour, cited by source in each table, and is provided so you can sanity-check any bid — it is not a quote, and your project will differ. Regulatory references are described in general terms for planning purposes, are subject to change, and are not legal advice; confirm current requirements with your own counsel and the governing agency for your project. Observations made during our work are field observations only and are not inspections or compliance determinations.